HAT 800-S

Electrical data
Type Primary nominal Primary current, RoHS since
RMS current measuring range 1) date code
IP N (A) IP M (A)
HAT 200-S 200 ±600 47143
HAT 400-S 400 ±1200 46115
HAT 500-S 500 ±1500 46129
HAT 600-S 600 ±1800 46115
HAT 800-S 800 ±2400 46115
HAT 1000-S 1000 ±2500 46097
HAT 1200-S 1200 ±2500 77271
HAT 1500-S 1500 ±2500 46158
UC Supply voltage (±5 %) 1) ±15 V
IC Current consumption ±20 mA
RINS Insulation resistance @ 500 V DC > 1000 MΩ
Uout Output voltage (Analog) @ ± I
P N, RL = 10 kΩ, TA = 25 °C ±4 V
Rout Output internal resistance 100 Ω
RL Load resistance > 10 kΩ
Accuracy – Dynamic performance data
ε Error @ IP N, TA = 25 °C (excluding offset) ≤ ±1 % of IP N
εL Linearity error 2) (0 … ± IP N) ≤ ±1 % of IP N
UO E Electrical offset voltage @ TA = 25 °C < ±20 mV
UO H Hysteresis offset voltage @ IP = 0,
after an excursion of 1 x IP N < ±10 mV
TCUO E Temperature coefficient of UO E −40 °C … +80 °C < ±1 mV/K
+80 °C … +105 °C < ±1.5 mV/K
TCUout Temperature coefficient of Uout (% of reading) < ±0.1 %/K
t
D 90 Delay time 3) to 90 % of IP N < 5 µs
BW Frequency bandwidth 4) (−3 dB) DC … 25 kHz
General data
TA Ambient operating temperature −40 … +105 °C
TS Ambient storage temperature −40 … +105 °C
m Mass 300 g
Standards EN 50178: 1997