LF 505-S/SP40

Electrical data

IP N Primary nominal RMS current 500 ( 630/10 sec. ) A
IP M Primary current, measuring range @ ±24 V 0 … ±1200 A
RM Measuring resistance
RM min RM max
with ±15 V @ ±500 A max 0 31 Ω
@ ±740 A max 0 3 Ω
with ±24 V @ ±500 A max 3 90 Ω
@ ±1000 A max 3 17 Ω
@ ±1200 A max 3 5 Ω
IS N Secondary nominal RMS current 143 mA
NP/NS Turns ratio 1 : 3500
UC Supply voltage (±5 %) 1) ±15 … 24 V
IC Current consumption 30 ( @ ±24 V) + IS mA

Accuracy – Dynamic performance data

εtot Total error @ I
P N, TA = 25 °C ±0.6 %
εL Linearity error < 0.1 %
Typ Max
IO Offset current @ IP = 0, TA = 25 °C ±0.45 mA
IO T Temperature variation of IO −25 °C … +70 °C ±0.3 ±0.50 mA
−40 °C … +70 °C ±0.5 ±0.80 mA
tD 90 Delay time to 90 % of the final output value for IP N step 2) < 1 µs
BW Frequency bandwidth (−1 dB) DC … 100 kHz

General data

TA Ambient operating temperature −40 … +70 °C
TA st Ambient storage temperature −40 … +85 °C
RS Resistance of secondary winding @ TA = 70 °C 56 Ω
m Mass 230 g
Standard EN 50155: 2021